4-146
03-09 Multi-function terminal S1-S4 type selection
Range
xxx0b: S1 A contact xxx1b: S1 B contact
xx0xb: S2 A contact xx1xb: S2 B contact
x0xxb: S3 A contact x1xxb: S3 B contact
0xxxb: S4 A contact 1xxxb: S4 B contact
03-10 Multi-function terminal S5-S8 type selection
Range
xxx0b: S5 A contact xxx1b: S5 B contact
xx0xb: S6 A contact xx1xb: S6 B contact
x0xxb: S7 A contact x1xxb: S7 B contact
0xxxb: S8 A contact 1xxxb: S8 B contact
Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally closed
switch/contact.
Each bit of 03-09/03-10 presents an input:
03-09= 0 0 0 0 0: normally open switch
s4 s3 s2 s1 1: normally close switch
03-10= 0 0 0 0 0: normally open switch
s8 s7 s6 s5 1: normally close switch
Example: S1 and S2 wired to a normally closed contact / switch set 03-09=0011.
Do not set the operation command parameter 00-02 to terminal control before setting the digital input type.
Failure to comply may cause death or serious injury.