4-122
the increasing frequency. When the speed is at 0~120Hz, the compensation amount is the same as that in
Torque compensation mode 0.
01-14 Input voltage setting
Range
200V: 155.0~255.0 V
400V: 310.0~510.0 V
575V: 540.0~670.0 V
690V: 648.0~804.0 V
The minimum input voltage of inverter is 0.1V.
Set the inverter input voltage (E.g. 200V / 208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V).
This parameter is used as a reference for predefined V/F curve calculation (01-00 = 0 to E), over-voltage
protection level, stall prevention, etc…
Note:It will depend on restore factory setting(13-08) to set the value of voltage
01-15 Torque compensation time
Range 1~1000 ms
Set the torque compensation delay time in milliseconds.
Only adjust in the following situations:
Increase value when:
When experiencing motor vibration
Decrease value when:
When motor torque response is too slow
01- 16 Maximum output frequency of motor 2
Range
5.0~599.0 Hz
01- 17 Maximum output voltage of motor 2
Range
200V: .1~255.0 V
400V: .2~510.0 V
575V: 0.1~670.0 V
690V: 0.1~804.0 V
01- 18 Middle output frequency 2 of motor 2
Range
0.0~599.0 Hz
01- 19 Middle output voltage 2 of motor 2
Range
200V: 0.0~255.0 V
400V: 0.0~510.0 V
575V: 0.0~670.0 V
690V: 0.0~804.0 V