4-236
10-30 Upper Limit of PID Target
Range
0 ~ 100 %
10-31 Lower Limit of PID Target
Range
0 ~ 100 %
Target value of PID will be limited to the range of upper & lower limit of PID target.
10-33 Maximum Value of PID Feedback
Range
1~10000
When the maximum value of PID feedback is active, it will become 100% the corresponding value of 10-02.
10-34 PID Decimal Width
Range
0~4
PID decimal width is used for rounding up setting. For example: set 10-34=1, it displays XXX.X ; set 10-34=2, it
displays XX.XX.
10-35 PID Unit
Range
0~21
PID unit is selected depending on user’s needs.
Note: When user switches PID in LED keypad, 10-33 is required to be lower than 1000 and 10-34=1, or the
keypad will show a SE05 alarm (PID setting error).
10-39 Output Frequency Setting of PID Disconnection
Range
00.00~599.00 Hz
When PID feedback disconnection is in alarm, frequency command output depends on the setting value of 10-39.
If the warning is lifted, PID control is restored.