4-163
Pulse input scaling, 100% = Maximum pulse frequency.
03- 32
Pulse input gain
Range
0.0~1000.0 %
Target value (03-03) in % = Pulse input frequency scaled to 100% based on maximum pulse frequency (03-31)
times the gain (03-32) + bias (03-33).
03-33
Pulse input bias
Range
-100.0~100.0 %
Target value (03-03) in % = Pulse input frequency scaled to 100% based on maximum pulse frequency (03-31)
times the gain (03-32) + bias (03-33).
03-34
Pulse input filter time
Range
0.00~2.00 Sec
* Refer to section 3.9 control circuit terminals for details.
* Refer to figure 4.4.27 for the pulse input specification.
Figure 4.4.27 Pulse input adjustment
Set Pulse Input Setup as Frequency Reference
Set parameter 00-05 to 4 and 03-30 to 0 to use the pulse input terminal PI as the frequency reference source.
Refer to Figure 4.3.5. for details. Next set the pulse input scaling (03-31), enter the pulse input frequency to match
the maximum output frequency. Adjust the pulse input filter time in case interference or noise is encountered.
Example: Pulse train input maximum 10 kHz, set parameter 03-31 to 10000 when maximum frequency is set to
60.0Hz.
Set Pulse Input as PID feedback value
Set parameter 00-05 to 5, 03-30 to 1 and PID feedback value source 10-01 to 3, to use the pulse input terminal PI
as the PID target (setpoint) value. Next set the pulse input scaling (03-31), enter the pulse input frequency to
match the maximum output frequency. Adjust the pulse input filter time in case interference or noise is
encountered. Refer to Figure 4.4.28.for details.
Note: The inverter will display a SE09 "PI setting error" when 03-30 = 1 and 10-01 is not set to 3.
Set Pulse Input as PID target value
Set parameter 00-05 to 5 and 03-30 to 2 to use the pulse input terminal PI as the PID target (setpoint) value. Next
set the pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency.
Adjust the pulse input filter time in case interference or noise is encountered. Refer to Figure 4.4.28.for details.
Note: The inverter will display a SE09 "PI setting error" if 03-30=0 and PID control is enabled (10-03 > 0).