4-247 
-  When DC voltage reaches the setting of 11-39 (stop voltage of OVP deceleration), it will decelerate based on 
the set value of 00-24 (Tdec4) 
 
-  Deceleration rate is linear based on the slope defined by the start point (11-38) and end point (11-39). 
 
4). Enable the OVP function with parameter 11-40 set to 1 or 2. The following parameter default values will be 
changed when the OVP function is enabled: 
 
07-12=1 (Stop mode: coast to stop) 
00-14(Tacc1)= 5.0 Sec(the frequency reference acceleration rate when DC voltage is too high.) 
00-22(Tdec3)= 20.0 Sec(low setting point of OVP deceleration rate). 
00-24(Tdec4)= 100.0 Sec(high setting point of OVP deceleration rate). 
 
Note: S curve should be disabled when using the OVP function (11-04~11-07=0.0sec). 
 
When 11-40=2: OV prevention Mode 2 
 
The process of OV prevention mode 2 is the same as that of OV prevention mode 1 but it strengthens more the 
part of DC BUS over the deceleration stop voltage of OV prevention (11-39) in Fig.4.4.92. It can accelerate 
frequency compensation to avoid OV protection by increasing frequency gain of OV prevention 2 (11-28).     
 
 
When 11-40=3: OV prevention Mode 3 
 
T=The inverter raise the output frequency temporarily to avoid OV, the output frequency wont higher than the 
value of 01-02 (Maximum Output Frequency of Motor 1).Please adjust the value of 01-02 according to application. 
If it still occur OV in 11-40=3, please raise the value of 11-64 in 0.1 unit.
 
11- 64  Acceleration Speed Gain Adjustment 
Range 
0.1~10.0 
 
It will influence the speed and current if the value of 11-64 is too high. 
 
11- 65  Target Main Circuit Voltage 
Range 
200V: 200V~400V 
400V: 400V~800V 
575V: 520V~1040V 
690V: 624V~1248V
 
 
11- 41  Reference frequency loss detection 
Range 
0: 
when reference frequency disappears, the deceleration will stop. 
1: when reference frequency disappears, continue to operate according to the proportion of 
reference frequency x 11-42.
 
 
11- 42  Reference frequency loss level 
Range 
0.0~100.0 % 
 
A Reference frequency loss is detected when the frequency command falls 90% within 360ms.   
 
The action performed when a reference loss is detected is set with parameter 11-41. 
 
11-41=0: Inverter will decelerate to a stop when a reference loss is detected. 
 
11-41=1:  Inverter will continue to operate; reference frequency is the value of Maximum Output Frequency of 
Motor 1 x the level set in parameter 11-42.