4-177
Figure 4.4.43 Acceleration / deceleration time reduction coefficient
04-05=5: DC braking current
Multi-function analog input AI2 can be used to adjust the DC Injection braking current.
DC braking current parameter 07-07 setting should be set to 0% to use this function.
The inverter rated current = 100%
Figure 4.4.44 DC braking current adjustment
04-05=6: Over-torque detection level
Multi-function analog input AI2 can be used to adjust the over-torque detection level.
100% of inverter rated current (V/F or V/F + PG control mode)
100% motor rated torque (SLV or SV control mode)
If the multi-function analog input is used to adjust the over-torque level, the internal over-torque detection level
(08-15) is disabled.