7-3
Momentary Contacts (Push Buttons)
Use push button / momentary switch to Run and Stop the inverter.
Set parameter 13-08 to 3, 5 or 7 for 3-wire program initialization, multi-function input terminal S1 is set
to run operation, S2 for stop operation and S7 for forward/reverse command.
00-01 Operation Method = 1
03-07 Terminal S7 Function = 26
Note: Stop mode selection can be set with parameter 07-09, default is deceleration to stop.