EasyManua.ls Logo

TECO A510s - Communication Parameters

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-48
Group 08: Protection Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
08-35
Motor Overheat
Fault Selection
0: Disable
0 - O O O O O O O
1: Deceleration to Stop
2: Free Run to top
3: Continue Running
08-36
PTC Input Filte
r
Time Constant
0.00 ~ 10.00 0.20 Sec O O O O O O O
08-37
Fan Control
Function
0: Start in operation
0 O O O O O O O
1: Permanent Start
2: Start in high
temperature (except of
the models of 2050,
4100 or the above)
08-38
Delay Time of Fan
Off
0~600 60 s O O O O O O O
08-39
Delay Time of
Motor Overheat
Protection
0~300 60 sec O O O O O O O
08-40
Motor2
Acceleration Stall
Prevention Level
20~200
HD:150
% O O O X X O O
ND:120
08-41
Motor2
Acceleration Stall
Prevention Limit
1~100 50 % O O O X X O O
08-42
PTC Protection
Level
0~10.0V 0.3 V O O O O O O O
08-43 PTC Restart Level 0~10.0V 1.2 V O O O O O O O
08-44
PTC Warning
Level
0~10.0V 0.6 V O O O O O O O
Group 09: Communication Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
09-00
INV
Communication
Station Address
1~31 1 - O O O O O O O *2
09-01
Communication
Mode Selection
0: MODBUS
0 O O O O O O O *5
1: Reserved
2: Reserved
3: Reserved
4: PROFIBUS*