4-49
Group 09: Communication Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
09-02
Baud Rate Setting
(bps)
0: 1200
4 - O O O O O O O *2
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
09-03 Stop Bit Selection
0: 1 Stop Bit
0 - O O O O O O O *2
1: 2 Stop Bit
09-04 Parity Selection
0: No Parity
0 - O O O O O O O *2 1: Even Bit
2: Odd Bit
09-05
Communication
Data Bit Selection
0: 8 Bit Data
0 - O O O O O O O *3
1: 7 Bit Data
09-06
Communication
Error Detection
Time
0.0~25.5
0.0 S O O O O O O O
09-07
Fault Stop
Selection
0: Deceleration to Stop
Based on Deceleration
Time 1 when
Communication Fault
Occurs.
3 - O O O O O O O
1: Coast to Stop when
Communication Fault
Occurs.
2: Deceleration to Stop
Based on Deceleration
Time 2 when
Communication Fault
Occurs.
3: Keep Operating when
Communication Fault
Occurs.
09-08
Comm. Fault
Tolerance Count
1~20
1 - O O O O O O O
09-09 Waiting Time
5~65
5 ms O O O O O O O
09-10 Reserved
* Selection of item 4 in parameter 09-01 is required to be coupled with the Profibus card.
* Parameter 09 does not be influenced by 13-08 (Restore Factory Setting)