TECO A510s - INV Communication Station Address; Baud Rate Setting (Bps); Stop Bit Selection; Communication Data Bit Selection

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-221
09-Communication Parameters
09-00 INV Communication Station Address
Range
1~31
09-02 Baud rate setting (bps)
Range
0:
1200
1:
2400
2:
4800
3:
9600
4: 19200
5: 38400
09-03 Stop bit selection
Range
0:
1 stop bit
1: 2 stop bits
09-04 Parity selection
Range
0:
No Parity
1: Even bit
2: Odd bit
09-05 Communication Data Bit Selection
Range
0:
8 Bit Data
1: 7 Bit Data
09-06 Communication error detection time
Range
0.0~25.5 Sec
09-07 Fault stop selection
Range
0:
Deceleration to stop based on deceleration time 1.
1: Coast to stop when communication fault occurs.
2: Deceleration to stop based on deceleration time 2
3: Keep operating when communication fault occurs.
09-08 Comm. fault tolerance count
Range
1~20
09-09 Waiting time
Range
5~65 msec
The Modbus communication port RJ45 (S+, S-) can be used to monitor, control, program and trouble-shoot the
inverter.
Modbus communication can perform the following operations, independent of the frequency command selection
(00-05) setting and Operation command selection (00-02) setting:
Monitor inverter signals
Read and write parameters.
Reset fault
Control multi-function inputs