4-221
09-Communication Parameters
09-00 INV Communication Station Address
Range
1~31
09-02 Baud rate setting (bps)
Range
0:
1200
1:
2400
2:
4800
3:
9600
4: 19200
5: 38400
09-03 Stop bit selection
Range
0:
1 stop bit
1: 2 stop bits
09-04 Parity selection
Range
0:
No Parity
1: Even bit
2: Odd bit
09-05 Communication Data Bit Selection
Range
0:
8 Bit Data
1: 7 Bit Data
09-06 Communication error detection time
Range
0.0~25.5 Sec
09-07 Fault stop selection
Range
0:
Deceleration to stop based on deceleration time 1.
1: Coast to stop when communication fault occurs.
2: Deceleration to stop based on deceleration time 2
3: Keep operating when communication fault occurs.
09-08 Comm. fault tolerance count
Range
1~20
09-09 Waiting time
Range
5~65 msec
The Modbus communication port RJ45 (S+, S-) can be used to monitor, control, program and trouble-shoot the
inverter.
Modbus communication can perform the following operations, independent of the frequency command selection
(00-05) setting and Operation command selection (00-02) setting:
Monitor inverter signals
Read and write parameters.
Reset fault
Control multi-function inputs