EasyManua.ls Logo

TECO A510s - UP; down Command Operation

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-138
Figure 4.4.20 Up / Down command timing diagram
UP / DOWN Command Operation
When the Forward Run command is active and the UP or Down command is momentarily activated the inverter
will accelerate the motor up to the lower limit of the frequency reference (00-13).
When using the UP / Down command, the output frequency is limited to the upper limit of frequency reference
(00-12) and the lower limit of frequency reference (00-13).
The UP / DOWN command uses acceleration 1 or 2 / deceleration time 1 or 2 for normal operation Tacc1 / Tdec1
(00-14, 00-15) or Tacc2 / Tdec 2 (00-16, 00-17).
*Refer to parameter 03-40 of UP/ Down frequency width setting for other functions of UP / Down.
03-0X =10: Acceleration/deceleration 1 selection
03-0X =30: Acceleration/deceleration 2 selection
Refer to the "multi-function digital input terminals select acceleration / deceleration time” page 4-76.
03-0X =11: Inhibit Acceleration/deceleration command (hold command)
When activated suspends the acceleration / deceleration operation and maintains the output frequency at current
level.
If 11-58 = 1, the frequency reference value is saved when the acceleration/deceleration inhibit command is active
the frequency reference value is saved. Deactivating the acceleration / deceleration inhibits command resumes
acceleration / deceleration and saved value will be erased.
If 11-58 = 1, the frequency reference value is saved when the acceleration/deceleration inhibit command is active,

Table of Contents

Related product manuals