4-253
- Droop function is disabled when 11-52 is set to 0.0%.
11-53: Droop control delay
This setting is used adjust the response speed of the droop function. Increase value in case of current oscillation.
11-54 Output KWHr initialization
Range
0:
Do not clear output KWHr
1: Clear output KWHr
Reset kW-hour meter (12-40).
11-55 STOP key selection
Range
0: Stop key is disabled when the operation command is not provided by operator.
1: Stop key is enabled when the operation command is not provided by operator.
11-55= 0: Stop button disabled when operation command is set for terminals (00-02=1) or communication
(00-02=3).
11-55= 1: Stop button enabled
11-56 UP/DOWN selection
Range
0:
UP/DOWN reference frequency adjustment with ENTER key.
1: UP/DOWN reference frequency adjustment without ENTER key.
11-56= 0: Changing the reference frequency on the keypad in UP/DOWN control requires the ENTER button to
be pressed for the inverter to accept the modified reference frequency.
11-56= 1: Changing the reference frequency on the keypad in UP/DOWN control immediately changes the
reference frequency and there for the output frequency.
Note: The reference frequency can be changed (up or down) via the keypad or by setting one of multi-functional
digital input terminals (03-00, 03-07) to 8 and 9. Refer to instructions of
(03-00 - 03-07 = 8 or 9).