4-52
Group 10: PID Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
10-36
~
10-38
Reserved
10-39
*Output
Frequency Setting
of PID
Disconnection
00.00~599.00 30.00 Hz O O O O O O O
10-40
Selection of PID
Sleep
Compensation
Frequency
0: Disable
0 O O O O O O O
1: Enable
* If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
11-00
Direction Lock
Selection
0: Allow Forward and
Reverse Rotation
0 - O O O O O O O
1: Only Allow Forward
Rotation
2: Only Allow Reverse
Rotation
11-01 Carrier frequency
0: Carrier Output
Frequency Tuning
1: 1KHz
2~16: 2~16KHz
* - O O O O O O O
11-02
Random PWM
Function Selection
0: Disable
0 - O O O O O O O
1: Enable
11-03
Automatic carrier
lowering selection
0: Disable
0 - O O X X X X O
1: Enable
11-04
S-curve Time
Setting at the Start
of Acceleration
0.00~2.50
0.20 s O O O O O O O

Table of Contents