Group 10: PID Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
10-18
Delay Time of PID
Sleep
0.0~255.5 0.0 s O O O O O O O
10-19
*Frequency of PID
Waking up
0.00~599.00 0.00 Hz O O O O O O O
10-20
Delay Time of PID
Waking up
0.0~255.5 0.0 s O O O O O O O
10-21
~
10-22
Reserved
10-23
PID Limit 0.00~100.0
100.0 % O O O O O O O *1
10-24
PID Output Gain 0.0~25.0
1.0 - O O O O O O O
10-25
PID Reversal
Output Selection
0: No Allowing Reversal
Output
0 - O O O O O O O
1: Allow Reversal Output
10-26
PID Target
Acceleration/
Deceleration Time
0.0~25.5
0.0 s O O O O O O O
10-27
PID Feedback
Display Bias
-99.99~99.99
0.00 - O O O O O O O
10-28
PID Feedback
Display Gain
0.00~100.00
100.00 - O O O O O O O
10-29
PID Sleep
Selection
0: Disable
1 - O O O O O O O
1: Enable
2: set by DI
10-30
Upper Limit of PID
Target
0.0 ~ 100.0 100.0 % O O O O O O O
10-31
Lower Limit of PID
Target
0.0 ~ 100.0 0.0 % O O O O O O O
10-32 Reserved
10-33
Maximum Value o