EasyManua.ls Logo

TECO A510s - Monitoring Parameters

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-56
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
Preventing
Oscillation
11-61
Time Parameter o
f
Preventing
Oscillation
0~100 0 O O X X X X O
11-62
Selection of
Preventing
Oscillation
0: Mode1
1 O O X X X X O
1: Mode2
11-63
Strong Magnetic
Selection
0: Disable
1 X X O O X X X
1: Enable
11-64
Acceleration
Speed Gain
Adjustment
0.1~10.0 1.0 - O X X X X X O
11-65
Target Main
Circuit Voltage
200V: 200V~400V 370
- O X X X X X O
400V: 400V~800V 740
575V: 520V~1040V 962
690V: 624V~1248V 1154
*: Refer to the attachment 1.
** If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz
Group 12: Monitoring Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
12-00
Display Screen
Selection (LED)
00000~77777
From the leftmost bit, it
displays the screen when
press DSP key in order.
0:no display
1: Output Current
2: Output Voltage
3: DC Bus Voltage
4: Heatsink Temperature*
5: PID Feedback
6: AI1 Value
7: AI2 Value
00000 - O O O O O O O
*1
*6
12-01
PID Feedback
Display Mode
(LED)
0: Display the Feedback
Value by Integer (xxx)
0 O O O O O O O *6
1: Display the Feedback
Value by the Value with
One Decimal Place
(xx.x)
2: Display the Feedback
Value by the Value with
Two Decimal Places
(x.xx)

Table of Contents

Related product manuals