4-55
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
11-46
Frequency Hold
Time at Stop
0.0~10.0 0.0 s O O O O O O O
11-47
KEB Deceleration
Time
0.0~25.5 0.0 s O O
X X X X
O *1
11-48
KEB Detection
Level
200V: 190~210 200
V O O
X X X X
O
400V: 380~420 400
575V: 540~570 555
690V: 540~684 555
11-49 Zero-servo Gain 0~50 5 - X X X O O X X
11-50 Zero-servo Count 0~4096 12 - X X X O O X X
11-51
Braking Selection
of Zero Speed
0: Disable
0 - O X X X X
X
O
1: Enable
11-52
Droop Control
Level
0.0~100.0% 0.0 % X X X O O X X *1
11-53
Droop Control
Delay
0.01~2.00 0.2 s X X X O O X X *1
11-54
Initialization of
Cumulative
Energy
0: Do not Clear
Cumulative Energy
0 - O O O O O O O *1
1: Clear Cumulative
Energy
11-55
STOP Key
Selection
0: Stop Key is Disabled
when the Operation
Command is not
Provided by Operator.
1 - O O O O O O O
1: Stop Key is Enabled
when the Operation
Command is not
Provided by Operator.
11-56
UP/DOWN
Selection
0: When Operator’s
UP/DOWN is Disabled,
it will be Enabled if
Press ENTER after
Frequency
Modification.
0 - O O O O O O O
1: When Operator’s
UP/DOWN is Enabled,
it will be Enabled after
Frequency
Modification.
11-57 Reserved
11-58
Record Reference
Frequency
0: Disable
0 - O O O O O O O *1
1: Enable
11-59
Gain of Preventing
Oscillation
0.01~2.50 * O O X X X X O
11-60 Upper Limit of 0~100 * % O O X X X X O

Table of Contents