4-333
4.6.2 Register and Data Format
Command Data (Read / Write)
Register No. Bit Content
2500H Reserved
2501H
Operation Signal
0 Operation Command 1 : Run 0 : Stop
1
Reverse Command 1 : Reverse 0 : Forward
2
External Fault 1 : Fault
3
Fault Reset 1 : Reset
4 Reserved
5 Reserved
6 Multi-function Comm S1 1 :“ON”
7 Multi-function Comm S2 1 :“ON”
8 Multi-function Comm S3 1 :“ON”
9 Multi-function Comm S4 1 :“ON”
A Multi-function Comm S5 1 :“ON”
B Multi-function Comm S6 1 :“ON”
C Multi-function Comm S7 1 :“ON”
D Multi-function Comm S8 1 :“ON”
E Inverter mode 1 : “ON”
F Torque Command set by Communication 1: “ON”
2502H *Frequency Command (Unit: 0.01Hz)
2503H Torque Command (+/-8192 corresponding to the rated torque +/-100%)
2504H Speed limit (+/- 120 corresponding +/-120%)
2505H AO1 (0.00V ~ 10.00V)
2506H
AO2 (0 ~ 1000): Voltage (corresponding to 0.00~10.00V); Current
( corresponding to 4mA~20mA)
2507H DO
2508H Reserved
2509H Reserved
250AH Reserved
250BH Reserved
250CH Reserved
250DH Reserved
250EH Reserved
250FH Reserved
2510H G12-00 H-WORD
2511H G12-00 L-WORD
Note: Write in zero for Not used BIT, do not write in data for the reserved register.
** If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz