Error history of automatic tuning
Range
0: No error
1: Motor data error
2: Stator resistance tuning error
3: Leakage induction tuning error
4: Rotor resistance tuning error
5: Mutual induction tuning error
6: Encoder error
7: DT Error
8: Motor’s acceleration error
9: Warning
Notes:
- Values are for 200V class, double the values for 400V class.
- In HD mode (00-27=0) the range is 0.0 to 400.0 Hz, 0.0 to 120.0Hz in for ND mode (00-27=1) and 0.0 to
599.0Hz is high frequency mode.
Auto-tuning
Based on the motor nameplate set the motor rated output power (17-01), motor output rated current (17-02),
motor rated voltage (17-03), motor rated frequency (17-04), motor rated speed (17-05) and number of motor
poles (17-06) to perform an auto-tune.
Automatic tuning mode selection (17-00)
Rotational auto-tuning (17-00=0) provide higher quality for motors.
After executing Rotational auto-tuning (17-00), Excitation current of motor 1 (02-09)Core saturation coefficient
1 of motor 1(02-10)Core saturation coefficient 2 of motor 1 and Core saturation coefficient 3 of motor 1 (02-12)
will renew the value.
Static auto-tuning (17-00=1) won’t rotate the motor while auto-tuning.
After executing Static auto-tuning (17-00=1),
Proportion of motor leakage inductance (02-33) and Motor slip
(02-34) will renew the value.
Stator resistance measurement (17-00=2) provide for long motor leads
After executing Stator resistance measurement (17-00=2), Resistance between wires of motor 1(02-15) will
renew the value.
Loop tuning (17-00=4) provide great response of current circuit, it can improve frequency bandwidth of current
and torque.
Rotation Auto-tuning Combination (17-00=5) is the auto-tuning for three in one, including Loop tuning (17-00=4)
Stator resistance measurement (17-00=2) and Rotational auto-tuning (17-00=0).
Static Auto-tune Combination (17-00=6) is the auto-tuning for three in one, including Loop tuning (17-00=4)
Stator resistance measurement (17-00=2) and Static auto-tuning (17-00=1)
Motor rated output power (17-01)
Set by inverter capacity (13-00)
Motor rated current (17-02)
Set by inverter capacity (13-00)
Set the range to 10 %~120 % of the inverter rated current.
Motor rated voltage (17-03)
Motor rated frequency (17-04)
Motor rated speed (17-05)