Chapter 8 Motor and Application Specific Settings
It is essential that before running the motor, the motor nameplate data matches the motor data in the
inverter.
8.1 Set Motor Nameplate Data (02-01, 02-05)
02-05 Rated power of motor 1
The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data
matches the motor rated capacity shown in parameter 02-05. The setting should only be changed when
driving a motor with a different capacity.
Range: 0.00 to 600.00 kW (1HP = 0.746 kW)
To set parameter 02-05:
- After power-up press the DSP/FUN key
- Set Group 02 (Motor Parameter), and select parameter -05 with the UP/DOWN ▲ and ▼ keys and
press the READ/ ENTER key.
Default values vary based on the inverter model.
02-01 Rated current of motor 1
The motor rated current is set at the factory based on the inverter model. Enter the motor rated current
from the motor nameplate if it does not match the value shown in parameter 02-01.
Setting range: 0.01 to 600.00A
To set parameter 02-01:
- After power-up press the DSP/FUN key
- Set Group 02 (Motor Parameter), and select parameter -01 with the UP/DOWN ▲ and ▼ keys and
press the READ/ ENTER key.