7-5
Examples:
Run Forward Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 01 12 C6
Run Reverse Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 03 93 07
Stop Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 00 D3 06
Note: The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section 4.5 of the
instruction manual for additional information.