4-190
Freq.
50 Hz
30 Hz
15 Hz
20 Hz
20s 25s 30s 40s
05-01
06-01
06-02
06-15
06-16 06-17 06-18
06-31
Figure 4.4.52 Single cycle automatic operation (stop)
Example 2:
Automatic operation mode – Continuous cycle
In this example the inverter repeats the same cycle.
Parameter Settings:
06-00 = 2 or 5 (Continuous cycle operation)
06-01~06-47= Enter the same setting as that of Example 1.
Figure 4.4.53 Periodic automatic operation