EasyManua.ls Logo

TECO A510s - Command Characteristic Selection of Master Frequency; Zero-Speed Operation Selection; Positive;Negative Analog Input as Main Frequency Reference Command

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-100
00- 28 Command characteristic selection of master frequency
Range
0: Positive characteristic (0-10V / 4-20mA = 0 -100%)
1: Negative / inverse characteristic (0-10V / 4~20mA = 100 - 0%)
00-28= 0: Positive reference curve, 0 – 10V / 4 – 20mA = 0 – 100% main frequency reference.
00-28= 1: Negative reference curve, 0 – 10V / 4 – 20mA = 100 – 0% main frequency reference.
Note: Selection applies to analog input AI1 and AI2.
100%
- 100%
-10V
10V
(20 mA)
0V
(4 mA)
Analog input
signal
Reference ( % )
Reference ( % )
-10V
10V
(20 mA)
0V
(4 mA)
Analog input
signal
(a) Normal / Positive Characteristics
(b) Inverse / Negative Characteristics
Figure 4.4.10 Positive/negative analog input as main frequency reference command.
00-29 Zero-speed operation selection
Range
0: Operation based on frequency command
1: Stop
2:
Operation based on lowest frequency
3: Zero-speed operation
Refer to figure 4.4.11 for zero-speed operation in sensor vector mode (SV / PMSV) (00-00=3 or 00-00=4).

Table of Contents