EasyManua.ls Logo

TECO A510s - Data Format Frame; Data Frame for ASCII Mode; Data Frame for RTU Mode

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-330
Data Format Frame
Data Frame for ASCII Mode
STX(3AH) Start Bit = 3AH
Node Address Hi
Communication Address(Station):
2-digit ASCII Code
Node Address Lo
Function Hi
Function Code (command):
2-digit ASCII Code
Function Lo
Command Start Address
Command Start byte:
4-digit ASCII Code
Command Start Address
Command Start Address
Command Start Address
Data length
The length of the command:
4-digit ASCII Code
Data length
Data length
Data length
LRC Check Hi
LRC Check Code:
2-digit ASCII Code
LRC Check Lo
END Hi
End Byte:
END Hi=CR(0DH), END Li = LF(0AH)
END Lo
Data Frame for RTU Mode
Master (PLC etc.) sends request to follower (inverter), and the follower sends a response to the master (PC, PLC).
The data received is illustrated here.
The data length varies depending on the command (Function).
Node Address
Function Code
DATA
CRC CHECK
Signal Interval
** The inverter response time is 10ms.
Node Address
00H: Broadcast to all the drivers
01H: to the No. 01 inverter
0FH: to the No.15 inverter
10H: to the No.16 inverter and so on...., max to No. 254 (FEH)
Function Code
03H: Read the register contents

Table of Contents

Related product manuals