4-98
When run command selection is external terminal control (00-02=1) and the inverter uses the jog frequency
(00-18, default 6.0 Hz) as its frequency reference with 03-00~03-07=6 or 7(6: Forward jog run command 7:
Reverse jog run command).The motor will run by the setting.
00-26 Emergency stop time
Range 0.0~6000.0 Sec
The emergency stop time is used in combination with multi-function digital input function #14 (Emergency stop).
When emergency stop input is activated the inverter will decelerate to a stop using the Emergency stop time
(00-26) and display the [EM STOP] condition on the keypad.
Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Figure 4.4.9 Emergency stop example
Multi-function digital input terminals (03-00 ~ 03-07) are set to 14: When the emergency stop input is activated the
inverter will decelerate to a stop using the time set in parameter 00-26.
Note: After an emergency stop command the run command and emergency stop command have to be removed
before the inverter can be restarted. Please refer to Figure 4.4.9. The emergency stop function can be used to
stop inverter in case of an external event.
Multi-function digital input terminals (03-00 ~ 03-07) set to 15: When the base block input is activated the inverter
output will turn off and the motor will coast to a stop.