4-135 
Table 4.4.7 Multi-speed operation selection 
Speed 
Multi-function digital input (S1 to S8) 
*3
 
Frequency selection 
Jog 
frequency 
reference 
Multi-speed 
frequency 4 
Multi-speed 
frequency 3
Multi-speed 
frequency 2
Multi-speed 
frequency 1 
1 0  0  0  0  0 
Frequency command 0( 05-01) or main 
speed frequency 
*2
 
2 0  0  0  0  1 
Auxiliary speed frequency    (04-05 = 0)
or frequency reference 1 ( 05-02) *3 
3  0  0  0  1  0  Frequency command 2 ( 05-03) 
4  0  0  0  1  1  Frequency command 3 ( 05-04) 
5  0  0  1  0  0  Frequency command 4 ( 05-05) 
6  0  0  1  0  1  Frequency command 5 ( 05-06) 
7  0  0  1  1  0  Frequency command 6 ( 05-07) 
8  0  0  1  1  1  Frequency command 7 ( 05-08) 
9  0  1  0  0  0  Frequency command 8 ( 05-09) 
10  0  1  0  0  1  Frequency command 9 ( 05-10) 
11  0  1  0  1  0  Frequency command 10( 05-11) 
12  0  1  0  1  1  Frequency command 11 ( 05-12) 
13  0  1  1  0  0  Frequency command 12 ( 05-13) 
14  0  1  1  0  1  Frequency command 13( 05-14) 
15  0  1  1  1  0  Frequency command 14 ( 05-15) 
16  0  1  1  1  1  Frequency command 15 ( 05-16) 
17 
1 
*1
 
─  ─  ─  ─  Jog frequency command (00-18) 
0: OFF, 1: ON, -: Ignore 
 
*1. Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.   
 
*2. When parameter 00-05=0 (frequency reference input = digital operator), multi-speed frequency 1 will be set by 
05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference input=control circuit 
terminal), multi-speed frequency command 1 is input through analog command terminal AI1 or AI2). 
 
*3. Multi-speed operation is disabled when PID is enabled.