4-189
06-Automatic Program Operation Parameters
06-00 Automatic operation mode selection
Range
0:
Disable
1, 4: Execute a single cycle operation. Restart speed is based on the previous stopped speed.
2, 5: Execute continuous cycle operation. Restart speed is based on the previous cycle stop
speed.
3, 6:
After completion of a single cycle, the on-going operation speed is based on the speed of the
last stage. Restart speed is based on the previous stopped speed
1 to 3: After a stop the inverter will start with the incomplete step when the run command is
re-applied.
4 to 6: After a stop the inverter will start with the first step of the cycle when the run command is
re-applied.
Automatic operation mode uses frequency reference parameters 05-01, 06-01~06-15, operation time parameters
06-16 ~ 06-31 and direction of operation parameters 06-32~06-47.
Notes:
The automatic operation mode is disabled when any of the following functions are active:
- Frequency wobbling function
- PID function
.
When automatic operation mode is active, external multi-step speed reference command 1~4 (03-00~03-07=2~5)
is disabled.
Example 1:
Automatic operation mode – Single cycle
In this example the inverter executes a single cycle and then stops.
Parameter Settings:
06-00 = 1 or 4 (Single cycle operation)
06-32~06-34= 1 (Forward for multi-step speed 0 - 2)
06-47= 2 (Reverse for multi-step speed 15)
06-35~06-46= 0 (Stop for multi-step speed 3 - 14)
05-01= 15 Hz (Multi-step speed 0: 15 Hz)
06-01= 30 Hz (Multi-step speed 1: 30 Hz)
06-02= 50 Hz (Multi-step speed 2: 50 Hz)
06-15= 20Hz (Multi-step speed 15: 20 Hz)
06-16= 20 sec (Multi-step speed 0: 20 sec)
06-17= 25 sec (Multi-step speed 1: 25 sec)
06-18= 30 sec (Multi-step speed 2: 30 sec)
06-31= 40 sec (Multi-step speed 15: 40 sec)