EasyManua.ls Logo

TECO A510s - Analog Inputs and Related Parameters; Gain and Bias Operations (for Frequency Reference Signal)

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-172
If AI2 is 0~10V, set parameter 04-00 to 0 or 2 and tune SW2 on the control board to V.
If AI2 is 0~20mA, set parameter 04-00 to 0 or 2 and tune SW2 on the control board to I.
If AI2 is 4~20mA, set parameter 04-00 to 1 or 3, tune SW2 on the control board to I.
If AI2 is 2~10V, set parameter 04-00 to 1 or 3, tune SW2 on the control board to V.
(1) Analog Input Level Adjustment AI1, AI2 (04-02, 04-03, 04-07, 04-08)
Each analog input AI1and AI2 has a separate gain and bias parameter associated with it.
Analog input signal AI1 can be adjusted with parameter 04-02 and 04-03; Analog input signal AI2 can be adjusted
with parameter 04-07 and 04-08. Refer to Figure 4.4.35.
Figure 4.4.35 Analog inputs and related parameters
Gain setting: Sets the level in % that corresponds to a 10V, -10V or 20mA signal at the analog input.
(Set the maximum output frequency 01-02 to 100 %)
Bias setting: Sets the level in % that corresponds to a 0V or 4mA signal at the analog input.
(Set the maximum output frequency 01-02 to 100%)
Use both gain and bias setting to scale the input signal.
Figure 4.4.36 Gain and bias operations (for frequency reference signal)

Table of Contents

Related product manuals