4-149
Table 4.4.8 Function table of multi-function digital output
Setting
Function
Contents
Control mode
Name LCD display V/F
V/F
+
PG
SLV SV
PM
SV
PM
SLV
SLV
2
0
During
Running
Running ON: During running (Run Command is ON) O O O O O O O
1
Fault contact
output
Fault
ON: Fault contact output (except CF00 and
CF01 )
O O O O O O O
2
Frequency
agree
Freq. Agree
ON: frequency agree (frequency agree
width detection is set by 03-14 )
O O O O O O O
3
Setting
frequency
agree
Setting Freq
Agree
ON: Output frequency = allowed frequency
detection level (03-13) ± frequency
bandwidth (03-14)
O O O O O O O
4
Frequency
detection 1
(> 03-13)
Freq. Detect 1
ON: Output frequency > 03-13
Hysteresis range is 03-14
O O O O O O O
5
Frequency
detection 2
(< 03-13)
Freq. Detect 2
OFF: Output frequency > 03-13
Hysteresis range is 03-14
O O O O O O O
6
Automatic
restart
Auto Restart ON: the period of automatic restart O O O O O O O
7 Reserved
Invalid Do
Func.
Reserved - - - - - - -
8 Reserved
Invalid Do
Func.
Reserved - - - - - - -
9 Baseblock Baseblock ON: During baseblock O O O O O O O
10 Reserved
Invalid Do
Func.
Reserved - - - - - - -
11 Reserved
Invalid Do
Func.
Reserved - - - - - - -
12
Over-Torque
Detection
Over Torque ON: Over torque detection is ON O O O O O O O
13 Current Agree Current Agree ON: when output current > 03-15 is ON O O O O O O O
14
Mechanical
Braking
Control
(03-17~18)
Invalid Do
Func.
ON: Mechanical braking release frequency
OFF: Mechanical braking run frequency
O O O O O O O
15 Reserved
Invalid Do
Func.
Reserved - - - - - - -
16 Reserved
Invalid Do
Func.
Reserved - - - - - - -
17 Reserved
Invalid Do
Func.
Reserved - - - - - - -
18 PLC status PLC statement
ON: when 00-02 is set to 3 (PLC operation
command source)
O O O O O O O
19
PLC control
contact
Control From
PLC
ON: Control from PLC O O O O O O O
20 Zero speed Zero Speed
ON: Output frequency < Minimum output
frequency (Fmin)
O O O O O O O
21 Inverter Ready Ready
ON: Inverter ready (after power on, no
faults)
O O O O O O O
22
Undervoltage
Detection
Low Volt
Detected
ON: DC bus voltage = < Low-voltage
warning detection level (07-13)
O O O O O O O