11-34 DC Voltage Filter Fall Amount
Range
0.00~1.00 V
11-35 DC Voltage Filter Deadband Level
Range
0.0~99.0 V
11-36 Frequency gain of OV prevention
Range
0.000~1.000
11-37 Frequency limit of OV prevention
Range
0.00~10.00 Hz
11-38 Deceleration start voltage of OV prevention
Range
200~400 V : 200V
400~800 V : 400V
575V: 500~1000V
690V: 600~1200V
11-39 Deceleration end voltage of OV prevention
Range
300~600 V : 200V
600~1200 V : 400V
575V: 500~1000V
690V: 600~1200V
11-40 OV prevention selection
Range
0:
Disable
1: OV prevention Mode 1
2: OV prevention Mode 2
3: OV Prevention Mode 3
Overvoltage suppression is used for the application of likely causing to energy recharge.
Example: there are two situations causing excessive energy to recharge the inverter in stamping application
(1) When cam clutch is not engaged, the motor will accelerate and start flywheel. When motor decelerates, the
rotation speed will higher than motor speed owing to the large flywheel’s inertia and then recharge the inverter.
(2) When cam clutch is engaged, the motor will start flywheel and compress the spring. When the highest point of
the cam moves beyond its center, the spring will release the power to the flywheel and excessive energy
output recharge the inverter.