4-145
03-0X =50: Unattended Start Protection (USP)
When input is active prevents inverter from starting automatically when a run command is present at time of
power-up. Please refer to Figure 4.4.24a for more details.
Figure 4.4.24a Unattended Start Protection
03-0X =51: Mode switching between speed and position control.
Refer to the parameter description of 21-09 ~ 21-41
Input Control
ON Position Control
OFF Speed Control
03-0X =52: Multi Position Reference Enable
Refer to the parameter description of 21-09~21-41
03-0X =53: 2-Wire Self-holding Mode (Stop Command)
Refer to parameter description of 00-02 (2-wire operation with self-holding function)
03-0X =58: Safety function
When safety function is on, the inverter will stop depending on the setting of 08-30 after the digital terminal is
active.
03-0X =62: EPS function
EPS input is valid when low voltage activate. Please refer to page 4-84
03-08 (S1~S8) DI scan time
Range
0: scan time 4ms
1: scan time 8ms
Set the digital input CPU scan time. The digital input signal needs to be present for the minimum scan time to
qualify as a valid command.
Note: For noisy environments select scan time of 8ms (results in a slower response time).