4-269
■ Verify: Compare Inverter Parameters against Keypad Parameters
16-09 Selection of keypad removed (LCD)
Range
0: Keep operating when LCD keypad is removed.
1: Display fault when LCD keypad is removed.
16-09=0: Continue operating when keypad is removed.
16-09=1: Trip inverter when keypad is removed while operating in local mode.
Steps LCD Display (English) Description
1
Select the copy function group (16) from the group menu.
2
Press the Read / Enter key and select parameter (16-07) copy sel.
3
Press the Read / Enter key to display the data setting / read screen
(LCD display is inversed).
4
Change the set value to 3 (verify) by using the up arrow key.
5
Use Read / Enter key to enable the read operation, the display is
shown as the left.
The bottom of LCD display will show a bar to indicate the read
progress.
6
-ADV-
VERIFY
COMPLETE
“VERIFY COMPLETE” will be displayed on the keypad when writing
was successful.
The error message of “VRYE Verify Error " may occur on the
keypad when writing parameters to the inverter is prohibited.
If the error is displayed, press any key to remove the error
message and go back to parameter 16-07.
7
When DSP/FUN key is pressed, the display returns to parameter
16-07.