Low Voltage Detection Level Function:
Wiring:
R/L1
S/L2
T/L3
3
~
S1~S8
24VG
AC Motor Drive
單相UPS或
電池
1-Phase UPS or Battery
440V Vac: 207~380
Vdc: 292~537
Execute Low Voltage
Detection Level Input
Notes for the emergency power supply. Please be aware of the following condition
when emergency power is ON:
1. Execute Low Voltage Function ON (DI=62),Fan doesn’t run.
2. Execute Low Voltage Function ON (DI=62),No phase loss.
3. Execute Low Voltage Function ON (DI=62),run frequency of motor depends on
the value of07-31
1
2
1
2
3
3
電磁接觸器動作時序圖
Before inputting emergency power, magnetic contactor ①and ③ are ON and
magnetic contactor ② should be OFF. Magnetic contactor ③ should be ON
after magnetic contactor is ON. Before removing battery and turning magnetic
contactor ② to be ON, Magnetic contactor ①and ③ should be OFF.
Relevant parameters:
07-30 Low Voltage Level Selection set 0 (Enable)
07-13
Low Voltage Detection Level set to 250V in 400 Class.
03-00~03-07 Set EPS input (62) enable.
07-31
Set Low Voltage Run Frequency