TECO A510s - Synchronized Operation Master Follower; Master Inverter Parameter Settings; Follower Inverter Parameter Settings

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-168
Figure 4.4.34 Synchronized operation master follower
Master inverter parameter settings:
1. Pulse output function selection: 03-35=1 (Pulse output is output frequency
2. Scale pulse output parameter 03-36 to 100% of output frequency
3. Set one of the Multi-function inputs Sn: 03-00 ~ 03-07=32 (Synchronization command)
Follower inverter parameter settings:
1. Frequency reference selection: 00-05=4 (Pulse input)
2. Pulse input’s function selection: 03-30=0 (Frequency command)
3. Pulse input scale: 03-31 (set the number of pulse in Hz to match maximum output frequency, 01-02)
4. Pulse input gain: 03-32 (Set the input gain of the pulse frequency set by 03-31
5. Pulse input bias: 03-33 (Set the input bias of the pulse frequency set by 03-31)
6. Pulse input’s filter time: 03-34 (if the pulse input is unstable due to the interference, increase value.)
7. Set one of the Multi-function inputs Sn: 03-00 ~ 03-07=32 (Synchronization command)
03-37 Timer ON delay (DIO)
Range
0.0~6000.0 Sec
03-38
Timer OFF delay (DIO)
Range
0.0~6000.0 Sec
Enable the timer function be setting one of multi-function input parameters 03-00~03-07 (S1 to S8) to 35 (timer
function input) and one of multi-function output parameters 03-11, 03-12 (R1A-R1C to R4A- R4C and PH1 to PH4)
to 27 (timer function output).
The timer function can be used to implement a timer relay. Use timing parameter 03-37 and 03-38 to set the timer
ON / OFF delay.
Timer output is turned ON when the multi-function timer input is ON for the time specified in parameter 03-37.