4-169
Timer output is turned OFF after the multi-function timer input is turned OFF for the time specified in parameter
03-38.
Timing example:
03- 41 Torque Detection Level
Range
0~300 %
03-42
Brake Release Delay Time
Range
0.00~65.00 Sec
Brake Release Function
It is required to be with the frequency agree function, as the following figure:
When the inverter starts running, if the output frequency > 03-13, and both frequency detection level and output
torque > torque detection level (03-41), it will delay the time of 03-42 to release brake.
It is recommended to be with starting and stopping frequency locked function (11-43~11-46), shown as the
following figure: