TECO A510s - Motor Overheat Fault Selection; PTC Input Filter Time Constant; Delay Time of Motor Overheat Protection; PTC Warning Level

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-219
Note : There is no 08-37=2 for the models of 2050, 4100 or the above.
08-35
Motor Overheat Fault Selection
Range
0:
Disable
1: Deceleration to Stop
2: Free Run to top
3: Continue Running
08-36
PTC Input Filter Time Constant
Range
0.00 ~ 10.00 sec
08-39
Delay Time of Motor Overheat Protection
Range
0~300 sec
08-42
PTC Protection Level
Range
0~10.0V
08-43
PTC Restart Level
Range
0~10.0V
08-44
PTC Warning Level
Range
0~10.0V
Motor Overheat Fault Selection
It execute motor overheat protection by the resistor (PTC) that built-in the motor.
the resistor (PTC) is between AI2 and GND and a divided resistor R ,as the pic 4.3.65(b)
08-35=0:
Motor overheats fault function is off.
08-35=1:
When the motor is overheating, it decelerates to stop.
08-35=2:
When the motor is overheating, it free runs to stop.
08-35=3:
When the motor is overheating, it does not stop running until reach the value of 08-42.
08-35=12: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of
08-44, the display will show
OH4 Motor Temp Warning and the motor will stop by 08-35=12.
08-35=3: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of
08-44, the display will show
OH3 Motor Temp Warningbut the motor continues running. But AI2 voltage level
is higher than the value of 08-42 and the time reach to 08-39, the motor free runs to stop.