4-219
Note : There is no 08-37=2 for the models of 2050, 4100 or the above.
08-35
Motor Overheat Fault Selection
Range
0:
Disable
1: Deceleration to Stop
2: Free Run to top
3: Continue Running
08-36
PTC Input Filter Time Constant
Range
0.00 ~ 10.00 sec
08-39
Delay Time of Motor Overheat Protection
Range
0~300 sec
08-42
PTC Protection Level
Range
0~10.0V
08-43
PTC Restart Level
Range
0~10.0V
08-44
PTC Warning Level
Range
0~10.0V
Motor Overheat Fault Selection
It execute motor overheat protection by the resistor (PTC) that built-in the motor.
the resistor (PTC) is between AI2 and GND and a divided resistor R ,as the pic 4.3.65(b)
08-35=0:
Motor overheats fault function is off.
08-35=1:
When the motor is overheating, it decelerates to stop.
08-35=2:
When the motor is overheating, it free runs to stop.
08-35=3:
When the motor is overheating, it does not stop running until reach the value of 08-42.
08-35=1、2: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of
08-44, the display will show
『OH4 Motor Temp Warning』 and the motor will stop by 08-35=1、2.
08-35=3: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of
08-44, the display will show
『OH3 Motor Temp Warning』but the motor continues running. But AI2 voltage level
is higher than the value of 08-42 and the time reach to 08-39, the motor free runs to stop.