Loading...
4-35
Group 04: External Analog Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
22: PID Output O O O O O O O
23: PID Target Value O O O O O O O
24: PID Feedback Value O O O O O O O
25: Output Frequency of
the Soft Starter
O O O O O O O
26: PG Feedback X O X O O X X
27: Reserved - - - - - - -
28: Communication
control
O O O O O O O
04-12 AO1 Gain 0.0~1000.0 100.0 % O O O O O O O *1
04-13 AO1 Bias -100.0~100.0 0 % O O O O O O O *1
04-14 Reserved
04-15 Reserved
04-16
AO2 Function
Setting
Range and definition are
the same as those of
04-11.
3 - O O O O O O O
04-17 AO2 Gain 0.0~1000.0 100.0 % O O O O O O O *1
04-18 AO2 Bias -100.0~100.0 0 % O O O O O - *1
04-19
AO2 Output Signal
Type
0: AO2 0~10V
0 - O O O O O O O
1: AO2 4~20mA
04-20
Filter Time of AO
Signal Scan
0.00~0.50 0.00 s O O O O O O O *1
Group 05: Multi-Speed Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
05-00
Acceleration and
Deceleration
Selection of
Multi-Speed
0: Acceleration and
deceleration time are
set by 00-14 ~ 00-24
0 - O O O O O O O
1: Acceleration and
Deceleration Time are
set by 05-17 ~ 05-48
05-01
*Frequency Setting
of Speed-Stage 0
0.00~599.00
5.00 Hz O O O O O O O *1
05-02
*Frequency Setting
of Speed-Stage 1
0.00~599.00 5.00 Hz O O O O O O O *1
05-03
*Frequency Setting
of Speed-Stage 2
0.00~599.00 10.00 Hz O O O O O O O *1
05-04
*Frequency Setting
of Speed-Stage 3
0.00~599.00 20.00 Hz O O O O O O O *1
05-05
*Frequency Setting
of Speed-Stage 4
0.00~599.00 30.00 Hz O O O O O O O *1

Table of Contents