4-256
12-Monitoring Parameters
12-00 Display screen selection (LED)
Range
Highest bit => 0 0 0 0 0 <= lowest bit
The value range of each bit is 0~7 from the highest bit to the lowest bit,
0:
No display
1: Output current
2: Output voltage
3: DC bus voltage
4: Heatsink temperature
5: PID feedback
6: AI1 value
7:
AI2 value
Note: The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the
display sequence see chapter 4.1.3.
12-01 PID feedback display mode (LED)
Range
0:
Display the feedback value in integer (xxx)
1: Display the feedback value with one place after the decimal point (xx.x)
2: Display the feedback value (x.xx) with two places after the decimal point
12-02 PID feedback display unit setting (LED)
Range
0:
xxxxx (no unit)
1: xxxPb (pressure)
2: xxxFL (flow)
12-05 Status display of digital input terminal (LED / LCD)
Range
Read-only
Terminals S1-S8 are represented using two segments of each digit. Segment turns on when input is active. The
bottom segments of each of the first three digits are used to represent the digital outputs (R1, R2, DO1).
Segments turn on when output is active.
Example1: S1~S8, R1, R2 and DO1 are ON