election
0: Disable
0 - O O OO X X O
1: Enable
07-01
Fault Auto-Restart
Time
0~7200 0 s O O O O O O O
07-02
Number of Fault
Auto-Restart
Attempts
0~10 0 - O O O O O O O
07-03 Reserved
07-04
Direct Start at
Power on
0: When the external run
command is enabled,
direct start at power up
0 - O O O O O O O
1: When the external run
command is enabled,
unable to direct start at
power-up.
07-05
Delay of Direct
Start at Power on
1.0~300.0 3.5 s O O O O O O O
07-06
DC Injection
Braking Starting
Frequency
0.0~10.0
0.5 HzO O OO X X O
07-07
DC Injection
Braking Current
0~100
50 % O O O O X X O
07-08
DC Injection
Braking Time at
Stop
0.00~100.00
0.50 s O O O O X X O
07-09
Stop Mode
Selection
0: Deceleration to Stop
0 - O O OO X X O
1: Coast to Stop
2: DC Braking Stop in All
Fields
3: Coast to Stop with
Timer
07-10
~
07-12
Reserved
07-13
Low Voltage
Detection Level
200V: 150~300 190
V O O O O O O O
400V: 250~600 380
575V: 500~600 546
690V: 500~600 546
07-14
Pre-excitation
Time
0.00~10.00 2.00 s X X O X X X X
07-15
Pre-excitation
Level
50~200 100 % X X O X X X X
07-16
DC Injection
Braking Time at
Start
0.00~100.00 0.00 s O O O O X X O
07-17 Reserved
07-18
Minimum Base
block Time
0.1~5.0 - Sec O O O O X O O