4-44
Group 07: Start /Stop Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
07-19
Direction-Detection
Speed Search
Operating Current
0~100 50 % O X O X X X O
07-20
Speed Search
Operating Current
0~100 20 % O X O X X X O
07-21
Integral Time of
Speed Searching
0.1~10.0 2.0 Sec O X O X X X O
07-22
Delay Time of
Speed Searching
0.0~20.0 0.2 Sec O O O O O X O
07-23
Voltage Recovery
Time
0.1~5.0 2.0 Sec O O O X X X O
07-24
Direction-Detection
Speed Search
Selection
0: Disable
0 - O O O X X X O
1: Enable
07-25
Low Voltage
Detection Time
0.00~1.00 0.02 Sec O O O O O O O
07-26
Start-up Mode
Selection of SLV
Coast to Stop
0: Start with speed
search
0 - X X O X X X X
1: Normal start
07-27
Start Selection
after Fault during
SLV Mode
0: Start with speed
search
0 - X X O X X X X
1: Normal start
07-28
Start after External
Base Block
0: Start with speed
search
0 - O X O X X X O
1: Normal start
07-29
Run Command
Selection at the
Action of DC
Braking
0: Not Allowable to Run
0 - O O X X X X X
1: Allowable to Run
07-30
Low Voltage Level
Selection
0: Disable
0 - X X X O O X X
1: Enable
07-31
**Low Voltage Run
Frequency
0.00~599.00 10.00 Hz X X X O O X X
07-32
Speed Search
Mode Selection
0: Disable
0 - O O O O X X X
1: Execute a Speed
Search at Power On
07-33
Start Frequency of
Speed Search
Selection
0: Maximum Output
Frequency of Motor
0 - O O O O X X X
1: Frequency Command
*07-13 Low Voltage Detection Level, it is enable when 07-30 Low Voltage Level Selection set 0 (Enable)
and lower frequency limit set to 250V.This application is for Emergency power supply (EPS)
* *If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz