4-204 
 
07-22  Delay time of speed searching 
Range 
0.0~20.0 Sec 
 
07-23  Voltage recovery time 
Range 
0.1~5.0 Sec 
 
07-24  Direction-Detection Speed Search Selection 
Range 
0: Disable 
1: Enable 
 
07-26  SLV Speed Search Function 
Range 
0: 
Enable 
1: Disable 
 
07-27  Start Selection after fault during SLV mode 
Range 
0:
 Start with speed search 
1: 
Normal start 
 
07-28  Start after external base block 
Range 
0:
 Start with speed search 
1: 
Normal start 
 
07-32  Speed Search Mode Selection 
Range 
0:
 Disable 
1: 
Execute a Speed Search at Power On 
 
07-33  Start Frequency of Speed Search Selection 
Range 
0:
 Maximum Output Frequency of Motor     
1: 
Frequency Command 
 
Speed search function is used to find the speed of a coasting motor and continue operation from that point. The 
speed search function is active after a momentary power loss. In V / F + PG or SV control mode (with PG control) 
speed search starts from the detected frequency (PG). 
 
Speed Search from Multi-function digital inputs 
 
Set the multi-function digital input to external speed search command 1 or 2. External speed search command 1 
(value = 19) and 2 (value = 34) cannot be set at the same time, otherwise "SE02" (digital input terminal error) 
warning occurs.   
 
Speed search function must be enabled before applying the run command to ensure proper operation. See relay 
logic in figure 4.4.64.