4-45
Group 08: Protection Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
08-00
Stall Prevention
Function
xxx0b: Stall prevention
is enabled in
acceleration.
0000b - O O O O O O O
xxx1b: Stall prevention is
disabled in
acceleration.
xx0xb: Stall prevention is
enabled in
deceleration.
xx1xb: Stall prevention is
disabled in
deceleration.
x0xxb: Stall prevention is
enabled in
operation
x1xxb: Stall prevention is
disabled in
operation
0xxxb: Stall prevention in
operation is
based on
deceleration time
of speed-stage 1.
1xxxb: Stall prevention in
operation is
based on
deceleration time
of speed-stage 2.
08-01
Stall Prevention
Level in
Acceleration
20~200
HD:150
ND:120
% O O O X X O O
08-02
Stall Prevention
Level in
Deceleration
200V: 330V~410V 385V
V O O O O X O O
400V: 660V~820V 770V
575V:900~1000 950V
690V:1080~1200 1140V
08-03
Stall Prevention
Level in Operation
30~200
HD:160
% O O X X X X O
ND:120
08-04 Reserved
08-05
Selection for Motor
Overload
Protection (OL1)
xxx0b: Overload
Protection is
disabled.
0001b - O O O O O O O
xxx1b: Overload
Protection is
enabled.
xx0xb: Cold Start of
Motor Overload
xx1xb: Hot Start of Motor