4-47
Group 08: Protection Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
08-17
Selection of
Low-Torque
Detection
0: Low-Torque Detection
is Disabled.
0 - O O O O O O O
1: Start to Detect when
Reaching the Set
Frequency.
2: Start to Detect when
the Operation is
Begun.
08-18
Selection of
Low-Torque
Operation
0: Deceleration to Stop
when Low Torque is
Detected.
0 - O O O O O O O
1: Display Warning when
Low Torque is
Detected. Go on
Operation.
2: Coast to Stop when
Low Torque is
Detected
08-19
Level of
Low-Torque
Detection
0~300 30 % O O O O O O O
08-20
Time of
Low-Torque
Detection
0.0~10.0 0.1 Sec O O O O O O O
08-21
Limit of Stall
Prevention in Acc
over Base Speed
1~100 50 % O O O X X O O
08-22
Stall Prevention
Detection Time in
Operation
2~100 100 ms O O O X X O O
08-23
Ground Fault (GF)
Selection
0: Disable
0 - O O O O O O O
1: Enable
08-24
External Fault
Operation
Selection
0: Deceleration to Stop
0 - O O O O O O O
1: Coast to Stop
2: Continuous Operation
08-25
Detection
Selection of
External Fault
0: Immediately Detect
when the Power is
Supplied.
0 - O O O O O O O
1: Start to Detect when
the Operation is
Started.
08-26
~
08-29
Reserved
08-30
Run Permissive
Function Selection
0: Deceleration to Stop
0 - O O O O O O O
1: Coast to Stop
08-31
Reserved
08-32
08-33
08-34