4-32
Group 03: External Digital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2 Attribute
from last set frequency
when stopped
3: Refresh frequency at
acceleration.
03-28
Photo-coupler
Output
Range and definition are
the same as those of
03-11, 03-12
0 - O O O O O O O
03-29
Photo-coupler
Output Selection
xxx0b: Photo-coupler A
Contact
xxx1b: Photo-coupler B
Contact
0000b - O O O O O O O
03-30
Selection of Pulse
Input
0: General Pulse Input
0 - O O O O O O O
1: PWM
03-31
Scale of Pulse
Input
Depending on the setting
of 03-30
03-30 = 0: 50~32000Hz
03-30 = 1:10~1000Hz
1000 Hz O O O O O O O *1
03-32
Pulse Input Gain
0.0~1000.0 100 % O O O O O O O *1
03-33
Pulse Input Bias
-100.0~100.0 0.0 % O O O O O O O *1
03-34
Filter Time of
Pulse Input
0.00~2.00 0.1 Sec O O O O O O O *1
03-35
Function Setting of
Pulse Output
1: Frequency Command
2 - O O O O O O O *1
2: Output Frequency
3: Output Frequency afte
r
Soft-Start
4: Motor Speed
5: PID Feedback
6: PID Input
7: PG Output (with PG
card)
03-36
Scale of Pulse
Output
1~32000 1000 Hz O O O O O O O *1
03-37
Timer ON Delay
(DIO)
0.0~6000.0 0.0 s O O O O O O O
03-38
Timer OFF Delay
(DIO)
0.0~6000.0 0.0 s O O O O O O O
03-39 Reserved
03-40
Up/Down
Frequency Width
Setting
0.00~5.00 0.00 Hz O O O O O O O
03-41
Torque Detection
Level
0~300 10 % X X O O O X X
03-42
Brake Release
Delay Time
0.00~65.00 0.00 s X X O O O X X
03-43
UP/DOWN
Acceleration/
Deceleration
0: Acceleration/
Deceleration Time 1
0 - O O O O O O O
1: Acceleration/

Table of Contents