4-31
Group 03: External Digital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2 Attribute
44: Reserved - - - - - - -
45: PID sleep O O O O O O O
46: Reserved - - - - - - -
47: Reserved - - - - - - -
48: Reserved - - - - - - -
49: Reserved - - - - - - -
50: Frequency Detection
3 (> 03-44+03-45)
O O O O O O O
51: Frequency Detection
4 (< 03-44+03-45)
O O O O O O O
52: Frequency Detection
5 (> 03-46+03-47)
O O O O O O O
53: Frequency Detection
6 (< 03-46+03-47)
O O O O O O O
03-13
Frequency
Detection Level
0.0~599.0 0.0 Hz O O O O O O O
03-14
Frequency
Detection Width
0.1~25.5 2.0 Hz O O O O O O O
03-15
Current Agree
Level
0.1~999.9 0.1 A O O O O O O O
03-16
Delay Time of
Current Agree
Detection
0.1~10.0 0.1 s O O O O O O O
03-17
**Mechanical
Braking Release
Level
0.00~599.00
0.00 Hz
O O O O O O O
03-18
**Mechanical
Braking Level Set
0.00~599.00
0.00 Hz
O O O O O O O
03-19
Relay (R1A-R2A)
Type
xxx0b: R1 A Contact
xxx1b: R1 B Contact
0000b - O O O O O O O
xx0xb: R2 A Contact
(DO2 for F1)
xx1xb: R2 C Contact
03-20 Reserved
03-21 Reserved
03-22 Reserved
03-23 Reserved
03-24 Reserved
03-25 Reserved
03-26 Reserved
03-27
UP/DOWN
Frequency
Hold/Adjust
Selection
0: Hold last set frequency
when stopped
0 - O O O O O O O
1: Set frequency to 0
when stopped
2: Allow speed changes