4-109
Example 2: After one or more parameters in 00-41 ~ 00-56 are set, user parameters settings are as
follows.
Step LCD Display Descriptions
1
Select the start parameter group (03) in the advanced modes.
2
PARA 13
-06. Access Level
-07. Password 1
-08. Initialize
Press (READ/ ENTER) and ▲ (Up) / ▼ (Down) key to enter the access
level of parameter (13-06).
3
Edit 13-06
Access Level
---------------------------------------
1
User Level
(0~2)
< 2 >
Press (READ/ ENTER) key to enter the screen of the data setting/ read.
* The selected setting value will flash.
4
─ADV─ G01-02
Access Level
1 User Level
(0-2)
< 2 >
Press ▲ (Up) / ▼ (Down) key to change setting value to 1 (13-06=1, user
level) and Press (READ/ ENTER) key to save the setting value (03-00).
Then, the digit stops flashing and the screen displays the setting value.
Few seconds later, the selected digit will flash again.
User level (13-06=1) can be set by one or more parameters in the user
parameters of 00-41 ~ 00-56. If users do not set user parameters, 13-06
will not be set in the user level (setting value=1).
5
PARA 13
-06. Access Level
Press (DSP/FUN) key to the display of subdirectory.
6
Group
00.User Function
Press (DSP/FUN) key to the display of group directory. It is required to
press ▲ (Up) key to select Group 00 User Function.
7
Monitor
Freq Ref
12-16=000.00Hz
-----------------------
---------------
12-17=000.00Hz
12-18=0000.0A
Press (DSP/ FUN) key to enter the main screen. If user would like to leave
the screen of user parameters, press RESET key and then DSP/FUN key
to select parameter Group 13. Hotkeys are only enabled in inverter
software V1.4.
8
Group
00. User Function00 User
13.Driver Status
13-06 can be selected to be adjusted so leave parameters or enter
parameter group 00 to edit user parameters is allowable.
9
PARA 00
-41. S1 Function Sel
Press (READ/ ENTER) key and ▲ (Up) / ▼ (Down) key to select user
parameter 0 (00-41) display.
Group
13 Driver Status
14 PLC Setting
15 PLC Monitor