10-3
LED display Description Cause Possible solutions
OL2
Inverter
overload
Inverter thermal overload
protection tripped.
If an inverter overload
occurs 4 times in five
minutes, it is required to
wait 4 minutes before
resetting the fault.
Voltage setting V/F mode too high,
resulting
in over-excitation of the motor.
Inverter rating too small.
Load too heavy.
Check V/f curve.
Replace inverter with
larger rating.
Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
Inverter output torque is
higher than 08-15 (over
torque detection level) for
the time specified in 08-16.
Parameter 08-14 = 0 to
activate.
Load too heavy.
Check over torque
detection parameters
(08-15 / 08-16).
Check and reduce motor
load, check and operation
duty cycle.
UT
Under
torque
detection
Inverter output torque is
lower than 08-19 (under
torque detection level) for
the time specified in 08-20.
Parameter 08-18 = 0 to
activate.
Sudden drop in load.
Belt break.
Check under torque
detection parameters
(08-19 / 08-20).
Check load / application.
run
Switch for
Motor1/Motor
2
Switch for Motor1/Motor2 in
running time
Execute command for switching
motor2 in running time
Execute command for switching
motor in running time
Revise the sequence
control and switch motor
in top time.
OS
Over speed
Motor speed exceeds level
set in 20-20 (PG Over
speed Level) for the time
set in 20-21 (PG over
speed time). Active when
20-19 (= 0 or 1).
This fault is active V/F + PG
and SV control mode
(00-00 = 1 or 3 or 4). Motor
speed can be monitored by
12-22
Motor speed overshoot (ASR)
PG ppr set incorrectly.
Overspeed parameters set
incorrectly.
Check ASR parameters
group 21.
Check PG parameters
Check overspeed
parameters 20-20/20-12.