10-6
LED display Description Possible causes Corrective action
CF07
Motor control
fault
Motor control fault SLV mode is unable to run motor.
Perform rotational or
stationary auto-tune
Increase minimum output
frequency (01-08)
FU
fuse open
DC bus fuse blown
DC fuse (Models 200V
50HP and above, 400V
75HP and above) open
circuit.
IGBT damaged.
Short circuit output terminals.
Check IGBTs
Check for short circuit at
inverter output.
Replace inverter.
CF00
Operator
Communic
ation Error
Errors of data transmission
occur in LCD keypad
LCD keypad and inverter cannot
transmit data after power on 5
seconds
Disconnect the operator
and then reconnect.
Replace the control board
LCD display
only*
CF01
Operator
Communic
ation Error
2
Errors of data transmission
occur in LCD keypad
LCD keypad and inverter can
transmit data but transmission
error occurs for more than 2
seconds
Disconnect the operator
and then reconnect.
Replace the control board
LCD display
only*
* When the communication errors occur in LED keypad, the LED will stay the screen and stop action.