11-13
600V class
Model
Horse
power
KVA
100% of rated
output current
HD/ND
Rated input current
HD/ND
Fuse rating
A510S-5001-H3(C3) 1
1.7 1.7/3.0 1.7/3.0
10
A510S-5002-H3(C3) 2
3 3/4.2 3/4.2
10
A510S-5003-H3(C3) 3
4.2 4.2/5.8 4.2/5.8
10
A510S-5005-H3(C3) 5
6.6 6.6/8.8 6.6/8.8
15
A510S-5008-H3(C3) 7.5
9.9 9.9/12.2 9.9/12.2
20
A510S-5010-H3(C3) 10
11.4 11.4/14.5 11.4/14.5
20
A510S-6015-H3(C3) 15
17.9 15/19 15/19
30
A510S-6020-H3(C3) 20
22.7 19/22 19/22
40
A510S-6025-H3(C3) 25
26.3 22/27 22/27
40
A510S-6030-H3(C3) 30
32.3 27/34 27/34
50
A510S-6040-H3(C3) 40
40. 34/42 34/42
80
A510S-6050-H3(C3) 50
50.2 42/52 42/52
80
A510S-6060-H3(C3) 60
64.5 54/62 54/62
100
A510S-6075-H3(C3) 75
74.1 62/80 62/80
125
A510S-6100-H3(C3) 100
103 86/99 86/99
150
A510S-6125-H3(C3) 125
118 99/125 99/125
200
A510S-6150-H3(C3) 150
156 131/147 131/147
250
A510S-6175-H3(C3) 175
175 147/163 147/163
300
A510S-6215-H3(C3) 215
194 163/212 163/212
300
A510S-6250-H3(C3) 270
229 192/216 192/216
400
A510S-6270-H3(C3) 300
258 216/246 216/246
400
Fuse type: Choose semiconductor fuse to comply with UL.
Class: CC, J, T, RK1 or RK5
Voltage Range:
For 200V class inverter, use 300V class fuse.
For 400V class inverter, use 600V class fuse.