Chapter 2  Installation and Configuration
Preparation
SuperLoader User’s Guide 15
•Bar code labels
Installation 
Location 
Requirements 2
The SuperLoader is designed to fit in a standard 19-inch rack using either 
the long or short brackets (depending on the depth of the rack) or the 
optional slide rail kit. When choosing an installation location, make sure 
that it meets the criteria found in table 2
 and table 3.
Table 2   Location 
Criteria
Requirement Description
Rack Size Standard 19 inch
Room Temperature 10 to 35 degrees C
(50 to 95 degrees F)
Power Source Line frequency: 50 to 60 Hz
Air Quality Good air quality with minimal sources of particulate 
contamination. Avoid placing the SuperLoader near 
cooling or exhaust vents, printing machines, frequently 
used doors and walkways, stacks of supplies that collect 
dust, and smoke-filled rooms.
Caution: Excessive dust or other debris in the tape path 
can damage tape and tape drives.
Humidity 20% to 80% relative humidity (non-condensing)
Minimum Clearance (to Facilitate 
Component Removal and 
Installation)
Front:
 27.0 in. (686 mm), including 2.0 in. (51 mm) from the 
front mounting rail to the inside of the front door. 
Rear:
 17.0 in. (432 mm). Using the appropriate 
SuperLoader bracket, ensure the rear door closes (see 
figure 10
).
Proximity to the Host Computer The SCSI bus maximum length is 39.37 ft. (12 m) including 
all SCSI bus lengths within the SuperLoader. The SCSI bus 
lengths are 16 in. (406.4 mm) per SuperLoader DLT/SDLT 
or 23.5 in. (596.9 mm) per SuperLoader LTO.