SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
101
2 Parameters
2.2 List of parameters
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0621, p0622
Description: Defines the ambient temperature of the motor for calculating the motor temperature model.
Dependency: Refer to: p0350, p0354
Note: The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
Description: Defines the rated overtemperature of the stator iron referred to ambient temperature in the motor temperature model
2 (p0612.1 = 1).
Dependency: For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Defines the rated overtemperature of the stator winding referred to the ambient temperature.
- motor temperature model 1 (I2t, p0612.0 = 1):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
p0605 is of significance for the rated temperature.
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
Overtemperature at the rated operating point.
- motor temperature model 2 (p0612.1 = 1):
Overtemperature at the rated operating point.
Dependency: For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically pre-assigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
The signal is not suitable as a process quantity and may only be used as a display quantity.
p0625[0...n] Motor ambient temperature during commissioning / Mot T_ambient
Access level: 3 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8017, 8018
Min Max Factory setting
-40 [°C] 80 [°C] 20 [°C]
p0626[0...n] Motor overtemperature, stator core / Mot T_over core
Access level: 4 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: 21_2 Unit selection: p0505 Func. diagram: 8018
Min Max Factory setting
10 [K] 200 [K] 50 [K]
p0627[0...n] Motor overtemperature, stator winding / Mot T_over stator
Access level: 2 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: 21_2 Unit selection: p0505 Func. diagram: 8017, 8018
Min Max Factory setting
15 [K] 200 [K] 80 [K]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals